Tonhe AN10 electric actuated water ball valve 1/4''-2'', different wiring, different working voltage :DC5V/12V/DC24V/AC/DC9-35V,IP67,NSF61, 1.3Mpa
Design feature
1 All-copper gear design, high accuracy output torque, especially for multi-channel scaling system.
2 Small size, compact structure.
3 A variety of control methods, either to accept remote valve position control signal, but also the feedback signal in place for computer intelligence unit testing.
4 Good sealing performance
For occasions
1 IC card water meter, heat meter.
2 Air-conditioning fan coil, fire sprinkler.
3 Solar energy drain valve, high efficiency water-saving.
4 Automatic control systems, university water system, small-scale industrial automation equipment, environmental protection.
Detail description
Valve size: AN10
Internal diameter: 10mm
Circulation medium: Fluid
Rated voltage: DC9-24V
Control signal:4-20mA/2-10V/1-5V
Output;4-20mA
Working current: ≤ 50mA
Open/close time: ≤ 7S
Extra long time: 50000 times
Body material: Stainless steel304
Actuator material: PPO
Airtight: Pressure 0.20PA, pressure maintaining 15s, Spillage≤ 0.122ml/s
Actuator rotation: 90°
Environment temperature: -15º C~50º C
Liquid temperature: 2º C~90º C
Manual override: No
Wire Diagram:
1,RD(red wire) connects to DC9-24V positive pole;
2,BK(black wire) connects to DC9 ~ 24V negative pole, and it is also 4-20mA-/0-5V-/0-10V's negative pole;
3,GR(green wire) connects to analogy signal positive pole(e.g. 4-20mA, 0-5V, 0-10V) ;
4,YW(yellow wire) connects to ERROR output negative pole. Wet contact NPN triode collector output. When there is an error causing the motor to work with excessive current, such as when debris blocks the valve and the ball cannot rotate, the contact is closed; when working normally, the contact open, it only can pull down the external signal. The load is 500mA
5,WT(white wire) connects to position feedback negative pole.
Wet contact NPN triode collector output, OC output PWM signal, 100Hz, 5%-95%, indicating 0-90 degrees. The load is 500mA.
*PWM: Connecting a pull-up resistor to WT and RD, usually use a 1k or 5.1k resistor, recommend to use 1k for power supply below 15V, and 5.1k for over 15V. Oscilloscope clamp connects to power's negative pole, and oscilloscope probe connects to PWM white wire.
*5%-95% represents duty cycle, which is the ratio of VCC time to the cycle time.
*PMW signal is a signal to give position feedback, the error signal needs to be connected with a 10k resistor to power's positive pole. When blocking occurs, the error signal to the ground voltage will be lower, at this time, it is able to test signal with oscilloscope.
Assemble Drawing :
Application:
Packing info:
Certification :
Workshop:
When you order the valves pls confirm below valve info :
Valve size:
valve material :
working voltage:
Actuator wire control :
Then Nadine will give you an reasonable price .
proportional control valve, AN10 flow control valve, electric regulating valve, electirc control valve , motorized control valve , motor power water valve